Wilkerson Instrument Co. Homepage A World of Signal Conditioning & Process Control Instrumentation Products


C Series
Variable Frequency
Drive

FEATURES

bullet

Volts / Hertz and Sensorless Vector Control (PWM by IGBT)

bullet

Motor Parameter Auto-tuning

bullet

150% Torque at 0.5Hz

bullet

0 ~ 400Hz Output Frequency

bullet

0 ~ 15kHz Carrier Frequency

bullet

Built-In Process PID Control

bullet

Ground Fault Protection

bullet

Built-in RFI Filter (Class A)

bullet

Built-in Potentiometer

bullet

Programmable I/O

bullet

PNP / NPN Selectable Signal Input

bullet

0 ~ 10Vdc Analog Output

bullet

Optional ModBus Communication Chip

SPECIFICATIONS

230V Class (0.5 ~ 5.4HP)

Model Number
(CI-xxx-G2)

000

001

002

003

Motor
Rating

HP

0.5

1

2

3

kW

0.4

0.75

1.5

2.2

Output
Ratings

Capacity [kVA]

0.95

1.9

3.0

4.5

FLA [A]

2.5

5

8

12

Voltage

200 ~ 230 V Three Phase 

Frequency

0 ~ 400 Hz

Input
Ratings

Voltage

200 ~ 230 V (± 10 %) Single Phase 

Frequency

50 ~ 60 Hz (± 5 %)

Weight [lbs]

1.92

1.96

3.95

4.1


  1. Indicates the maximum applicable capacity when using 4 pole standard motor.
  2. Rated capacity ( 3*V*I) is based on 220V for 200V class and 440V for 400V class.
  3. Maximum output voltage will not be greater than the input voltage. Output voltage less than the input voltage can be set.

Common:

CONTROL

Control method

V/F control, Sensorless vector control

Frequency setting resolution

Digital reference : 0.01 Hz (below 100 Hz), 0.1 Hz (over 100 Hz)
Analog reference : 0.03 Hz / 50 Hz

Frequency accuracy

Digital: 0.01 % of max. output frequency
Analog: 0.1 % of max. output frequency

V/F ratio

Linear, Square, User V/F

Overload capacity

150 % of rated current for 1 min., 200% for 30 seconds
(characteristic is inversely proportional to time)

Torque boost

Auto/Manual torque boost

OPERATION

Input Signal

Operator Control

3 digit LED keypad, terminals, ModBus communications (optional)

Frequency setting

Analog : 0 ~ 10V / 4 ~ 20 mA, Digital: keypad, Communication: ModBus, Potentiometer

Start signal

forward, reverse

Multi-step speed

Up to 8 speeds can be set (use multi-function terminal)

Multi Step accel/decel time

0 ~ 6,000 sec, Maximum 8 pre-defined steps using multi-function terminals

Emergency stop

Interrupts the output of the inverter

Jog

Jog operation

Fault reset

Reset faults when protective function is active

Output Signal

Operating status

Frequency detection, Overload alarm, stalling, overvoltage, undervoltage, inverter overheating, running, stop, constant speed, speed searching

Fault output

Relay and Open Collector Output

Indicator

Output frequency, output current, output voltage, DC bus voltage

Protection

Inverter trip

Overvoltage, undervoltage, overcurrent, inverter overheating, motor over heating, input/output phase loss, input/output miss-wiring, overload protection, communication error, CPU error, hardware fault, external device fault 1 and 2

Inverter alarm

Stall prevention, overload alarm

Environment

Ambient temperature

-10 °C ~ 50 °C 

Storage temperature

-20 °C  ~ 65 °C 

Ambient humidity

90 % RH max.(Non condensing)

Altitude vibration

1,000m above sea level, Max. 5.9m/sec²(=0.6g)

Application site

No corrosive gas, combustible gas, oil mist, or dust

Cooling method

Forced air cooling

ORDERING INFORMATION

230V
Model Motor Rating

HP

kW

CI-000-C2-1P

0.5

0.4

CI-001-C2-1P

1

0.75

CI-002-C2-1P

2

1.5

CI-003-C2-1P

3