Wilkerson Instrument Co. Homepage A World of Signal Conditioning & Process Control Instrumentation Products


H Series
Variable Frequency
Drive

FEATURES

bulletVoltage Ratings:

200-230 VAC, 3 phase
380-460 VAC, 3 phase

bullet50 hp to 350 hp
bulletInverter Type: PWM with IGBT
bulletControl Method: Volts / Hertz with Space Vector Technology
bulletProgrammable V/F pattern (Custom curves)
bulletAuto and manual selectable torque boost
bulletAuto energy saving
bulletMultiple stall prevention modes
bulletBuilt-in PI control
bulletSlip compensation for optimal performance
bulletState of art window based drive software
bulletOn board diagnostics
bullet7 multiple programmable speeds
bulletAdjustable carrier frequency up to 15 kHz
bulletRestart from instantaneous power failure
bulletStall prevention
bullet6 programmable multifunction input terminals and 4 output terminals
bullet2 & 3 wire operation
bulletSpeed search
bulletRemovable Keypad (Able to read & write parameter for drive cloning)
bulletProgrammable auto restart after and during trip
bulletRestart from instantaneous power failure
bulletCE UL cUL ISO9001

DESCRIPTION

The H Series is designed for high starting torque applications with IGBT module, Space Vector PWM control algorithm and 32-bit DSP (Digital Single Processor).

Built in PI control enables cost-effective speed regulation of fan and pumps by precise flow, pressure and temperature control. The optimized current and torque control by space vector PWM algorithm and 32-bit DSP enhance power factor by exact torque calculation.

The H Series adapts Space Vector PWM Control algorithm, which allows low THD (Total Harmonic Distortion) and low torque, & current ripples, thereby improves output voltage utility, prevents motor & inverter overheats and enhances power factor of motor.

The H Series has a user-friendly interface and versatile protection functions that make it enable to maximize its capability and to operate motors without trips.

SPECIFICATIONS

460V Class (40 - 125HP)

Model Number
(CI-xxx-H4)

050 060 075 100

125

Applicable Motor

Constant Torque (HP)

40 50 60 75

100

Constant Torque (kW)

30 37 45 55

75

Variable Torque (HP)

50 60 75 100 125

Variable Torque (kW)

37 45 55 75 90

Output Ratings

Constant Torque (FLA)

61 75 91 110

152

Variable Torque (FLA)

52 62 74 80 160

Input Ratings

Input Voltage

3 Phase, 380 to 460 V (± 10%)

Input Frequency

50 to 60 Hz (± 5%)

Weight (lbs)

99

99 139 139

150

460V Class (125 - 300HP)

Model Number
(CI-xxx-H4)

150

200

250

300

350

Applicable Motor

Constant Torque (HP)

125

150

175

215

300

Constant Torque (kW)

90

110

132

160

220

Variable Torque (HP)

150 200 250 300 350

Variable Torque (kW)

110 132 160 185 280

Output Ratings

Constant Torque (FLA)

183

223

264

325

432

Variable Torque (FLA)

228 264 330 361 477

Input Ratings

Input Voltage

3 Phase, 380 to 460 V (± 10%)

Input Frequency

50 to 60 Hz (± 5%)

Weight (lbs)

216

2165

269

269

386

All Models:

Output Ratings

Max. Frequency

0.5 to 400 Hz

Output Voltage

3 Phase, 0 to Input Voltage

Control

Control Method

Space Vector PWM

Frequency Resolution

0.01 Hz

Frequency Accuracy

0.01% of Maximum Frequency (Digital Setting)
0.1% of Maximum Frequency (Analog Setting)

V/F Ratio

Linear, Non-linear, User Programmable

Braking Torque(w/o DB)

About 20%

Overload Capacity CT

150% for 1 minute

Overload Capacity VT

120% for 1 minute

Torque Boost

0 to 20% programmable

Operating

Operation Method

Key-pad Control
Terminal Control
Remote (Option)

Frequency Setting

Analog: 0 to 10 V / 4 to 20 mA
Digital: using Key-pad

Acceleration /
Deceleration Time

0.1 to 6,000 sec
8 Pre-defined Acc. / Dec. Ramp (Programmable)

Multi-Step

8 Preset Operation Speed (Programmable)

Programmable I/O

Programmable Input

6 Programmable Inputs

Programmable Output

5 Programmable Outputs

Protective
Functions

Inverter Trip

Overvoltage, Undervolatage, Overcurrent, Fuse Open, Ground Fault, Inverter Overheat, Motor Overheat, Main CPU Error.

Stall Prevention

Over-current Prevention

Instant Power Failure

Below 15 msec: continuous operation
Over 15 msec: auto restart (programmable)

Operating
Condition

Ambient Temperature

14 °F to 104 °F (-10 °C to 40 °C)

Humidity

Below 90% Relative Humidity (Non Condensing)

Altitude

Less than 3,300ft (1,000m) without de-rating

Cooling System

Forced Air Cooling

ORDERING INFORMATION

460V

Model Motor Ratings

Constant Torque Application (1)

Variable Torque Application (1)

HP

kW

HP

kW

CI-050-H4

40

30

50 / 60

30

CI-060-H4

50

37

60 / 75

37

CI-075-H4

60

45

75

45

CI-100-H4

75

55

100

55

CI-125-H4

100

75

125

75

CI-150-H4

125

90

150

90

CI-200-H4

150

110

200

110

CI-250-H4

175

132

250

132

CI-300-H4

225

160

300

160

CI-350-H4

300

220

350

220

 

  1. Overload rating is 150% for one minute, 200% for 0.5 seconds.  Variable Torque (VT) Overload rating is 110% for one minute, 150% for 0.5 seconds
  2. Horsepower is based on "typical" NEMA B 4 pole motor design. Always select according to the motor rated current.