SPECIFICATIONS
Except where noted all specifications apply to operation at +25ºC
INPUTS
Field selectable: 0-30 mV, 0-200 mV, ±15 mV, ±100 mV
RATIOMETRIC
Deviation less than 0.1% of full scale, ± 1 count, with ±10% variation in excitation voltage.
DISPLAY
Bright, large, 0.56" (14.2 mm) high efficiency red LED. 4½ digits + extra zero may be switched on to display ±19,999(0). Leading zeros blanked.
CALIBRATION RANGE
0 mV input may be set anywhere in range of the meter. 200 mV may be set anywhere above or below 0 mV input.
ISOLATED POWER SUPPLY
Selectable 5 VDC or 10 VDC ± 5% @ 50 mA or 24 VDC ± 5% @ 20 mA.
Use to power either strain gauge or 4-20 mA output signal, (maximum load resistance of 1200 W).
PEAK HOLD
Captures peak reading and displays it via the front panel ENTER button.
PEAK HOLD INDICATION
Front panel LED
TARE
Captures/sets current display to zero via front panel TARE button.
Programmable tare: automatically sets tare to a preset value.
TARE INDICATION
Front panel LED
ACCURACY
0.05% of full scale, ± 1 count
NON-VOLATILE MEMORY
All programming values are stored in non-volatile memory for ten years if power is lost.
ZERO STABILITY
0.5 µV/°C
SPAN STABILITY
0.005% of full scale /°C
LOCKOUT
Switch 8 at rear of instrument restricts modification of programmed values.
INPUT IMPEDANCE
20 kilohms
POWER
115 VAC or 230 VAC ±10%, 50/60 Hz, 10 VA
ISOLATION
AC power: 1500 VAC
DC power: 500 VDC
ENVIRONMENTAL:
Operational Ambient Temperature Range: 0 to 60°C
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
ALARM POINTS
4, any combination of high or low alarms
ALARM STATUS INDICATION
Front panel LED
ALARM DEADBAND
0-100% of full scale, user selectable
RELAYS