 |
Accepts Current, Voltage, Thermocouple, and RTD Inputs
|
 |
Easy Four-Button Programming and Setup with Lockout Capability
|
 |
Display: Steady, 4 Digits, (-1999 to 9999), 0.56" High
|
 |
Factory Calibrated for All Inputs
|
 |
Type 4X, NEMA 4X, IP65 Front
|
 |
Modern, Rugged, Shallow Depth Case; Only 3.1" Behind Panel
|
 |
Extra-Large Bezel for Rough Panel Cutouts
|
 |
Universal Power Supply: 85-265 VAC or 90-265 VDC
|
 |
Optional 24 VDC Operation
|
 |
Serial Communication Options RS-232, RS-422/485
|
 |
Copy Meter Settings to Other Meters
|
 |
Meters in NEMA 4 Enclosures Approved as UL & c-UL Systems
|
 |
3 Year Warranty
|
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
DISPLAY
Bright, large, 0.56" (14.2 mm) high efficiency red LED.
Four digit (-1999 to 9999), automatic lead zero blanking.
FRONT PANEL
Type 4X, NEMA 4X, IP65. Panel gasket provided.
PROGRAMMING METHODS
Four front panel push buttons, PC and MeterView software, or cloning with Copy feature.
NOISE FILTER
This function averages any minor or quick changes in the input signal and displays the reading with greater stability. Increasing the filter value will help stabilize the display. Programmable between 2 and 199 (to disable filter program 0).
DISPLAY UPDATE RATE
Process/RTD: 3.7-5/sec; T/C: 1.8-2.5/sec
OVERRANGE
Display flashes 9999
UNDERRANGE
Display flashes -1999
RECALIBRATION
All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
MAX/MIN DISPLAY
The maximum and minimum readings reached by the process are stored until reset by the user or until power to the meter is turned off.
PASSWORD
User programmable
NON-VOLATILE MEMORY
All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
POWER
AC: 85 - 265 VAC, 50/60 Hz, 4 VA; DC: 90-265 VDC, 4 W.
Option: 12-36 VDC. DC powered units are reverse polarity protected.
FUSE
Recommended external fuse: 0.5 A, 250 V slow blow
NORMAL MODE REJECTION
64 dB at 50/60 Hz
ISOLATION
4 kV per High Voltage Test
ENVIRONMENTAL
Operating temperature range: 0 to +65°C
Storage temperature range: -40 to +85°C
Relative humidity: 0 to 90% non-condensing
CONNECTIONS
Power & Signal: removable screw terminal blocks accept 12 to 26 AWG. Serial: RJ11 header, standard on all meters.
ENCLOSURE
1/8 DIN, high impact plastic, UL 94V-0, color; gray
OVERALL DIMENSIONS
2.45" x 4.68" x 3.72"
(62 mm x 119 mm x 95 mm) (H x W x D)
WEIGHT
8 oz (2.27 g)
UL & C-UL APPROVAL
Pending
UL FILE NUMBER
CE MARK
Pending
WARRANTY
3 years parts and labor
EXTENDED WARRANTY
Warranty may be extended an additional 12 months by returning the Product Registration Form within 2 months from date of purchase.
COLD JUNCTION REFERENCE
Automatic
TEMPERATURE DRIFT
±2°C maximum; 0 to 65°C ambient temperature
OFFSET ADJUSTMENT
Programmable to ±19.9°. This parameter allows the user to apply an offset value to the temperature being displayed.
INPUT IMPEDANCE
Greater than 100 kilohms
SENSOR BREAK DETECTION
Indicated by display flashing OPEN
.
SERIAL COMMUNICATION ADAPTERS
COMPATIBILITY
Compatible with EIA-232 or EIA-422 & EIA-485
CONNECTORS
PC compatible 9-pin D subminiature connector (RS-232) or removable 5-pin screw terminal connector (RS-422/485) and RJ11 to meter
DISTANCE
Meter to adapter: 7' (1.8 m), RS-232 adapter to PC: 50' (15 m) maximum, RS-422/485 adapter to PC: 3,937' (1,200 m) maximum
METERVIEW SOFTWARE
REMOTE PROGRAMMING
MeterView software allows all setup parameters to be programmed from a PC and saved to a file for reporting or programming other meters.
DATA ACQUISITION
MeterView software provides a convenient way to collect the data generated by the Trident’s serial output. The user can select the logging time interval. Data is written to an ASCII file that could then be imported into a spreadsheet or other application.
ORDERING INFORMATION