Wilkerson Instrument Co. Homepage A World of Signal Conditioning & Process Control Instrumentation Products


DM4051
STRAIN GAUGE INPUT
FIELD RANGEABLE
ISOLATED TRANSMITTER

FEATURES
bulletAllows Inputs of 0.5mV/V to 128mV/V
bulletProvides a Fully Isolated DC Output Proportional to Strain Gauge Input
bulletSelectable Response Time/Filter
bulletUser-Settable Input and Output Ranges
bulletConnections and Ranging Readily Accessible From The Front
bulletFully Labeled Jumper Positions for Easy Range Settings
bulletUser Write-on Label
bulletPlug-in Terminal Blocks
bulletStandard DIN rail Mount With Easy Snap-on Snap-off
bulletChoice of Power Options
bulletPermanent Warranty
bulletUL, cUL Certified


DESCRIPTION

The DM4051 provides an isolated voltage or current output proportional to a strain gauge (bridge) input.

The field rangeable product provides 10V excitation and has gold plated jumpers to select the following ranges and functions:
    
     Input Range and Output Range
     Elevated or Suppressed Offset
     Bandwidth Range
     Voltage or Current Output
     Normal or Reverse Acting Output

Connections are made via two 4-pin plug-in terminal blocks. These terminal blocks allow the product to be removed without unwiring the connections.

TYPICAL APPLICATIONS

Measurement of output from load cells, pressure transmitters, and strain gauge sensors. Eliminates ground loops and common mode signals. Single-unit replacement module provides all normal input and output ranges.

MOUNTING

The module mounts on a standard H-35 DIN rail. A spring latch holds it in place. The module is demounted by using a screw driver to release the latch. The latch release is accessible at the bottom of the module.

SPECIFICATIONS

INPUT 
Impedance
  >5 megohms

Excitation
  10 VDC, 35 mA maximum

Range
  0.5 mV/V to 128 mV/V

Offset
  ±0% to ±100% span

Span Adjustment
  +5% to -55% of selected span

Zero Adjustment
  ±30% of selected span

POWER
Wattage 2.5W maximum

AC (Standard)
  115 VAC  ±10%, 50/60 Hz
  230 VAC  ±10%, 50/60 Hz
  24 VAC   ±10%, 50/60 Hz
 
DC (Optional)
  24 VDC (21 to 32 VDC)

OUTPUT
Voltage
0/.25
0/1
1/5
0/5
0/10
-5/5
-10/10
Current (mA)
0/1
0/4
4/20
0/20
OUTPUT LOGIC
Normal or Reverse Acting

DRIVE CAPABILITY
Voltage 
  5 mA
Current 
  >24 V compliance

ACCURACY
±0.1% of span

LINEARITY
±0.01% of span

OUTPUT RIPPLE
<0.1% of full scale
  (peak to peak)

RESPONSE TIME (99%)
0.02, 0.2, 2, 20 sec

OPERATING TEMPERATURE
-10 to +60°C
 14 to 140°F

TEMPERATURE STABILITY
±0.01% of span per°C

ISOLATION
Resistance
  >500 megohms
Voltage Rating
  >1000 VAC sine wave

COMMON MODE REJECTION
>120 dB, DC to 60 Hz

APPROVALS
UL, cUL Certified


TERMINAL CONNECTIONS

Power AC L1 or DC +
Power AC L2 or DC -
Input Signal +
Input Signal -
Excitation +
Excitation -
Output +
Output -

(Terminal Labeled)

L1
L2
Input +
Input -
EXC.+
EXC.-
Output +
Output -