DM4130
THERMOCOUPLE INPUT
ISOLATED, FIELD RANGEABLE
TRANSMITTER
FEATURES
 | Spans from 6.25% to 100% of T/C Range |
 | Linearized for J, K, R, S, T, E, and N Thermocouples |
 | Provides a Fully Isolated DC Output Proportional to T/C Input |
 | Plug-in Output Terminal Block |
 | Standard DIN rail Mount With Easy Snap-on Snap-off |
 | Connections and Ranging Readily Accessible From The Front |
 | User-Settable Input and Output Ranges |
 | Fully Labeled Jumper Positions for Easy Range Settings |
 | Choice of Power Options |
 | User Write-on Label |
 | Permanent Warranty |
 | UL, cUL Certified |
DESCRIPTION
The DM4130 provides an isolated voltage or current output proportional to
temperature as measured with a thermocouple. Any thermocouple may be used, and
types J, K, R, S, T, E, and N can be linearized.
A microprocessor controls span and offset settings, performs cold junction
compensation calculations, and performs a table look-up for linearization.
The DM4130 includes filtering and conditioning to reduce susceptibility to
transients and noisy operations. It utilizes a feedback VCO to develop a pulse
train with a duty cycle proportional to the input signal amplitude. This pulse
train is coupled through a pulse transformer to the output circuitry, where the
duty cycle data is converted to a proportional DC output level.
Connections are made via two 4-pin terminal blocks. The lower terminal block is
unpluggable, allowing the product to be removed without unwiring the output and
power connections.
TYPICAL APPLICATIONS
Useful for temperature monitoring, control and data acquisition.
MOUNTING
The module mounts on a standard H-35 DIN rail. A spring latch holds it in place.
The module is demounted by using a screw driver to release the latch. The latch
release is accessible at the bottom of the module.
SPECIFICATIONS
INPUT
Minimum
Span
Adjustment
(5 mV input
minimum)
Maximum
100% of T/C
range
Offset
Adjustment
0% to 90% of T/C range
LINEARIZATION
±0.25°C of NIST tables
full range of J, K, R, S, T, E,
N
COLD JUNCTION COMPENSATION
+\-0.25°C accuracy
IMPEDANCE
1 megohm
UPDATE PERIOD
4/sec
POWER
Wattage 2.5 W
maximum
AC (Standard)
115 VAC ±10%, 50/60 Hz
230 VAC ±10%, 50/60
Hz
24 VAC ±10%, 50/60
Hz
DC
(Optional)
24 VDC (21-32
VDC)
APPROVALS
UL, cUL Certified
|
OUTPUT
Voltage
0/.25
0/1
1/5
0/5
0/10
-5/5
-10/10
|
Current
(mA)
0/1
0/4
4/20
0/20
|
OUTPUT LOGIC
Normal or Reverse Acting
DRIVE CAPABILITY
Voltage
5 mA
Current
>24 V compliance
ACCURACY
±0.1% of span
OUTPUT RIPPLE
<0.1% of full scale
(peak to peak)
OPERATING TEMPERATURE
14 to 140°F
-10 to 60°C
TEMPERATURE STABILITY
±(.01% of span)/°C
ISOLATION
Resistance
>500 megohms
Voltage Rating
>1000 VAC Sinewave
COMMON MODE REJECTION
>120 dB, DC to 60 Hz
|
| TERMINAL CONNECTIONS
Power AC L1 or DC +
Power AC L2 or DC -
T/C Input
+
T/C Input
-
Shield
Output
+
Output
-
|
(Terminal
Labeled)
L1
L2
1
2
3
Output +
Output - |
|