Wilkerson Instrument Co. Homepage A World of Signal Conditioning & Process Control Instrumentation Products


DR4380 A
DC INPUT FIELD RANGEABLE
ISOLATED TRANSMITTER

FEATURES
bulletProvides a Galvanic Isolated DC Output Proportional to DC Input
bullet50 mV or 1 mA Minimum Input Span
bullet256 V or 100 mA Maximum Input Span
bulletPlug-in Screw Terminal Blocks
bullet21 to 28 VDC Power
bulletDIN Rail Mount - Case Only 0.5" Wide
bullet3 Year Warranty
bulletUL/cUL Recognized


DESCRIPTION

The DR4380A provides an isolated DC voltage or current output proportional to a DC voltage or current input. The input and output can be ranged in the field utilizing slide DIP switches. Zero and Span controls provide ±26% adjustability.

The DR4380A provides 3 way isolation between input, output, and power source. The isolation makes the product useful for measuring input signals with high common mode voltages and for breaking ground connections to eliminate ground loops. Its wide choice of inputs and outputs allow signal conversion and scaling as well.

The screw terminal blocks plug into the case, which allows easy wiring and removal of products.

All of the DR Series of products provide transient protection to help eliminate damage from lightning and from other transients created on the power and signal leads.

TYPICAL APPLICATIONS

Eliminates ground loops and common mode signals for voltage/current scaling or conversion, isolation, buffering, noise reduction. Single-unit replacement module provides all normal input and output ranges.

MOUNTING

All DR Series products are designed to mount on a 35 mm DIN rail. The products feature a steel mounting clip, with a compression spring, for secure mounting.

SPECIFICATIONS

INPUT
Voltage
  Select any range between
  ± 50 mV to ± 256 V
   (Minimum span 50 mV)
   (Maximum span 256 V)

Current
  Select any range between
  ±1 mA to ±100 mA, internal shunt
   (Minimum span 1 mA)
   (Maximum span 100 mA)

INPUT IMPEDANCE
Voltage
  400 kilohms

Current
  Current Input 40 ohms

OUTPUT
Voltage
1/5
0/5
0/10
-5/5
-10/10
Current (mA)
0/1
4/20
0/20

BANDWIDTH
-3dB at 3 Hz

OUTPUT RIPPLE
<0.1% of span
 
(peak to peak)

ACCURACY
±0.1% of span

LINEARITY
±0.05% of span

COMMON MODE REJECTION
100 dB, DC to 60 Hz

ISOLATION,OUTPUT/INPUT/POWER
>500 megohms
1500 VAC rms

OPERATING TEMPERATURE
 
14°F to 158°F
-10°C to 70°C

TEMPERATURE STABILITY
±(0.01% of span)/°C max

POWER
21 to 28 VDC, 60 mA max


TERMINAL CONNECTIONS
Power DC +
Power DC - 
Input +
Input -
Output +
Output -
(Terminal Labeled)
24 VDC +
24 VDC -
Input +
Input -
Output +
Output -