P Series
Specialized Fan & Pump Control
Variable Frequency
Drive
FEATURES
|
Variable torque rating for HVAC & pump | |
|
Sensorless and space vector control | |
|
150% torque in overall range | |
|
Motor parameter auto-tuning | |
|
High speed 32 bits digital signal processor | |
|
0.7~15Hz carrier frequency | |
|
Build in multi-motor control (up to 4) | |
|
Built-in process PID control | |
|
Up/down & 3-wire operational function | |
|
Built-in ModBus (RP485) communication | |
|
0~10VDC, -10~+10VDC analog input | |
|
PNP/NPN selectable signal input | |
|
External NTC input | |
|
Optional braking unit | |
|
Cooling fan On/Off control | |
|
Optional extendable sub-boards, (ProfiBus & DeviceNet) |
APPLICATIONS
|
HVAC systems | |
|
Building automation systems | |
|
Centrifugal fans and pumps | |
|
Water and waste treatment | |
|
Blowers | |
|
Chillers |
SPECIFICATIONS
230V Class (7.5 ~ 40HP)
|
Model Number |
007 |
010 |
015 |
020 |
025 |
030 |
040 | |
|
Motor |
HP |
7.5 |
10 |
15 |
20 |
25 |
30 |
40 |
|
kW |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 | |
|
Output |
Capacity [kVA] |
9.1 |
12.2 |
17.5 |
22.9 |
28.2 |
33.5 |
46 |
|
FLA [A] |
24 |
32 |
46 |
60 |
74 |
88 |
122 | |
|
Voltage |
3 Phase, 200 ~ 230 V |
|||||||
|
Frequency |
0 ~ 400 Hz |
|||||||
|
Input |
Voltage |
3 Phase, 200 ~ 230 V (± 10 %) |
||||||
|
Frequency |
50 ~ 60 Hz (± 5 %) |
|||||||
|
Weight [lbs] |
16.5 |
17.0 |
30.4 |
31.5 |
42.8 |
44.1 |
48 | |
460V Class (7.5 ~ 40HP)
|
Model Number |
007 |
010 |
015 |
020 |
025 |
030 |
040 | |
|
Motor |
HP |
7.5 |
10 |
15 |
20 |
25 |
30 |
40 |
|
kW |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 | |
|
Output Ratings |
Capacity2 [kVA] |
9.1 |
12.2 |
18.3 |
22.9 |
29.7 |
34.3 |
45 |
|
FLA [A] |
12 |
16 |
24 |
30 |
39 |
45 |
61 | |
|
Frequency |
0 ~ 400 Hz |
|||||||
|
Voltage |
380 ~ 460 V 3 |
|||||||
|
Input Ratings |
Voltage |
3 Phase, 380 ~ 460 V (± 10 %) |
||||||
|
Frequency |
50 ~ 60 Hz (± 5 %) |
|||||||
|
Weight [lbs] |
17.0 |
17.0 |
30.6 |
31.7 |
44.1 |
44.1 |
48 | |
Common:
|
CONTROL |
Control Method |
V/F Control, (Sensorless Vector PWM) |
||
|
Frequency Setting Resolution |
Digital Reference: 0.01 Hz (Below 99 Hz), 0.1 Hz (100
Hz & over) |
|||
|
Frequency Accuracy |
Digital: 0.01 % of Max. Output Frequency |
|||
|
V/F Ratio |
Linear, Squared Pattern, User V/F |
|||
|
Overload Capacity |
|
|||
|
Torque Boost |
Manual Torque Boost (0 ~ 15 %), Auto Torque Boost |
|||
|
OPERATION |
Input Signal |
Operator Control |
32 character LCD keypad • Terminals • Modbus RTU Communication, RP485, ProfiBus-DP, DeviceNet, F-Net |
|
|
Frequency Setting |
Analog: 0 ~ 10V / 4 ~ 20mA / Additional port for Sub-Board (0 ~ 10V) |
|||
|
Start Signal |
Forward, Reverse |
|||
|
Multi-Step |
Up to 8 Speeds can be Set (Use Multi-Function Terminal) |
|||
|
Multi Step Accel/Decel Time |
0 ~ 6000 seconds. Maximum 8 pre-defined steps using multi-function terminals |
|||
|
Emergency Stop |
Interrupts the Output of Inverter |
|||
|
Jog |
Jog Operation |
|||
|
Auto Operation |
Operates from Internal Sequence by Setting Multi-Function Terminal (5 Way * 8 Step) |
|||
|
Fault Reset |
Trip Status is Removed when Protection Function is Active |
|||
|
Output Signal |
Operating Status |
Frequency Detection Level, Overload Alarm, Stalling, Over Voltage, Under Voltage, Inverter Overheating, Running, Stop, Constant Speed, Fault output (Relay and Open collector) Inverter By-Pass, Speed Searching, Auto-Operation Step, Auto-Operation Sequence |
||
|
Fault Output |
Contact Output (30A, 30C, 30B) – AC250V 1A, DC30V 1A |
|||
|
Indicator |
Choose 1 from Output Frequency, Output Current, Output Voltage, DC Voltage Output Torque (Output Voltage: 0 ~ 10V) |
|||
|
Protective Function |
Inverter Trip |
Over Voltage, Under Voltage, Over Current, Fuse Open, Ground Fault, Inverter Overheating, Motor Overheating, Output Phase Open, |
||
|
Inverter Alarm |
Stall Prevention, Overload Alarm, Temperature Sensor Fault |
|||
|
Display |
Keypad |
Operation Information |
Output Frequency, Output Current, Output Voltage, Frequency Value Setting, Operating Speed, DC Voltage |
|
|
Trip Information |
Indicates a Fault when the Protection Function activates, Retains Up to 5 Faults |
|||
|
Environment |
Ambient Temperature |
-10 °C ~ 40 °C (14 °F ~ 104 °F) |
||
|
Storage Temperature |
-20 °C ~ 65 °C (-4 °F ~ 149 °F) |
|||
|
Ambient Humidity |
90 % RH Max.(Non-Condensing) |
|||
|
Altitude - Vibration |
Below 1,000m or 3,300ft · Below 5.9m/sec˛(=0.6g) |
|||
|
Application Site |
No Corrosive Gas, Combustible Gas, Oil Mist, or Dust |
|||
|
Cooling Method |
Forced Air Cooling |
|||
ORDERING INFORMATION
| 230V | ||
| Model | Motor Rating | |
|
HP |
kW |
|
| CI-007-P2 |
7.5 |
5.5 |
| CI-010-P2 |
10 |
7.5 |
| CI-015-P2 |
15 |
11 |
| CI-020-P2 |
20 |
15 |
| CI-025-P2 |
25 |
18.5 |
| CI-030-P2 |
30 |
22 |
| CI-040-P2 |
40 |
30 |
| 460V | ||
| Model | Motor Rating | |
|
HP |
kW |
|
| CI-007-P4 |
7.5 |
5.5 |
| CI-010-P4 |
10 |
7.5 |
| CI-015-P4 |
15 |
11 |
| CI-020-P4 |
20 |
15 |
| CI-025-P4 |
25 |
18.5 |
| CI-030-P4 |
30 |
22 |
| CI-040-P4 |
40 |
30 |