S Series
Variable Frequency
Drive
FEATURES
| Voltage Ratings: |
200-230 VAC, 3 phase
380-460 VAC, 3 phase
| 1 HP to 100 HP | |
| Enclosure: IP00~IP20 | |
| Inverter Type: PWM with IGBT | |
| Control Method: Sensorless Vector with Space Vector Technology | |
| 1~15 kHz Carrier Frequency | |
| 0~ 400 Hz Output Frequency | |
| Removable Keypad (Able to read & write parameter for drive cloning) | |
| Intelligent Accel/Decel for Trip-Free Operation | |
| State of art window based drive software | |
| On board diagnostics | |
| Auto Tuning | |
| 3 Multi-Function Inputs | |
| 2 Multi-Function Output | |
| Built-in PID Control | |
| Pre-Set Speeds | |
| 2 & 3 wire operation | |
| Multi-step Programmable Run Patterns | |
| Auto Torque Boot | |
| DC Injection Braking | |
| Stall Prevention | |
| Built-In Braking Circuit on 1~10 HP units | |
| CE UL cUL ISO9001 |
DESCRIPTION
The S Series is an open loop flux vector drive. It has a built-in PID algorithm that controls flood, temperature, pressure, etc. through the proportional, integral and differential calculus between the feedback value and reference value. The high speed CPU performs the calculation effortlessly and quickly.
The auto-tuning algorithm in S Series sets the motor factors automatically is designed to identify your motor's equivalent circuit prior to operation. A proprietary auto-tuning feature performs a series of tests, based upon information found on the motor nameplate. Auto-tuning resolves the traditional commissioning difficulties in low speed by the load variation and the low torque.
The S Series has several additional I/O boards that can be easily mounted into the connection terminal on control board. Each I/O board is standardized for a specific I/O requirement. The three main I/O boards are "Sub-board A", "Sub-board B" and "Sub-board C". This helps system engineer design most adequate and cost-effective system using the exactly necessary number of I/Os and functions. It is extendable and changeable in case of system upgrade or change. The control parameters and detailed functions for these boards are not shown until any of them is inserted.
SPECIFICATIONS
230V Class (1 ~ 30HP)
|
Model Number |
001 |
002 |
003 |
005 |
007 |
010 |
015 |
020 |
025 |
030 |
|
|
Motor |
HP |
1 |
2 |
3 |
5 |
7.5 |
10 |
15 |
20 |
25 |
30 |
|
kW |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
|
|
Output |
Capacity [kVA] |
1.9 |
3.0 |
4.5 |
6.1 |
9.1 |
12.2 |
17.5 |
22.9 |
28.2 |
33.5 |
|
FLA [A] |
5 |
8 |
12 |
16 |
24 |
32 |
46 |
60 |
74 |
88 |
|
|
Frequency |
0 ~ 400 Hz (Sensorless Vector Control: 0 ~ 300Hz, Sensored Vector Control: 0 ~ 120 Hz) |
||||||||||
|
Voltage |
200 ~ 230 V |
||||||||||
|
Input |
Voltage |
3 Phase, 200 ~ 230 V (± 10 %) |
|||||||||
|
Frequency |
50 ~ 60 Hz (± 5 %) |
||||||||||
|
Dynamic |
Braking Circuit |
On Board |
On Board |
On Board |
Optional (Braking Unit, Resistor) |
||||||
|
Average Braking Torque |
100% |
100% |
100% |
150% |
|||||||
|
Max. Continuous Baking Time |
5 seconds |
5 seconds |
5 seconds |
Controlled by Braking Unit |
|||||||
|
Max. Duty |
30 % ED |
30 % ED |
30 % ED |
10 % ED |
|||||||
|
Weight [lbs] |
4.6 |
4.6 |
4.8 |
4.9 |
7.5 |
7.7 |
13.8 |
14.3 |
19.4 |
20 |
|
230V Class (40 ~ 75HP)
|
Model Number |
040 |
050 |
060 |
075 |
|
|
Motor |
HP |
40 |
50 |
60 |
75 |
|
kW |
30 |
37 |
45 |
55 |
|
|
Output |
Capacity [kVA] |
46 |
55 |
68 |
84 |
|
FLA [A] |
122 |
146 |
180 |
220 |
|
|
Frequency |
0 ~ 400 Hz (Sensorless Vector Control: 0 ~ 300Hz, Sensored Vector Control: 0 ~ 120 Hz) |
||||
|
Voltage |
3 Phase, 200 ~ 230 V |
||||
|
Input |
Voltage |
3 Phase, 200 ~ 230 V (± 10 %) |
|||
|
Frequency |
50 ~ 60 Hz (± 5 %) |
||||
|
Dynamic |
Braking Circuit |
Optional (Braking Unit, Resistor) |
|||
|
Average Braking Torque |
150% |
||||
|
Max. Continuous Baking Time |
Controlled by Braking Unit |
||||
|
Max. Duty |
10 % ED |
||||
|
Weight [lbs] |
42 |
42 |
61 |
61 |
|
460V Class (1 ~ 30HP)
|
Model Number |
001 |
002 |
003 |
005 |
007 |
010 |
015 |
020 |
025 |
030 |
|
|
Motor |
HP |
1 |
2 |
3 |
5 |
7.5 |
10 |
15 |
20 |
25 |
30 |
|
kW |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
|
|
Output Ratings |
Capacity2 [kVA] |
1.9 |
3.0 |
4.5 |
6.1 |
9.1 |
12.2 |
18.3 |
22.9 |
29.7 |
34.3 |
|
FLA [A] |
2.5 |
4 |
6 |
8 |
12 |
16 |
24 |
30 |
39 |
45 |
|
|
Frequency |
0 ~ 400 Hz (Sensorless Vector Control: 0 ~ 300Hz, Sensored Vector Control: 0 ~ 120 Hz) |
||||||||||
|
Voltage |
380 ~ 460 V 3 |
||||||||||
|
Input Ratings |
Voltage |
3 Phase, 380 ~ 460 V (± 10 %) |
|||||||||
|
Frequency |
50 ~ 60 Hz (± 5 %) |
||||||||||
|
Dynamic |
Braking Circuit |
On Board |
On Board |
On Board |
Optional (Braking Unit, Resistor) |
||||||
|
Max. Braking Torque |
100% |
100% |
100% |
150% |
|||||||
|
Max. Continuous Baking Time |
5 seconds |
5 seconds |
5 seconds |
Controlled by Braking Unit |
|||||||
|
Max. Duty |
30 (3) % ED |
30 (2) % ED |
30 % ED |
10 % ED |
|||||||
|
Weight [lbs] |
4.7 | 4.7 | 4.8 | 4.9 | 7.5 | 7.7 | 13.8 | 14.3 | 19.4 | 20 | |
460V Class (40 ~ 100HP)
|
Model Number |
040 |
050 |
060 |
075 |
100 |
|
|
Motor |
HP |
40 | 50 | 60 | 75 | 100 |
|
kW |
30 | 37 | 45 | 55 | 75 | |
|
Output Ratings |
Capacity2 [kVA] |
45 | 56 | 68 | 82 | 100 |
|
FLA [A] |
61 | 75 | 91 | 110 | 152 | |
|
Frequency |
0 ~ 400 Hz (Sensorless Vector Control: 0 ~ 300Hz, Sensored Vector Control: 0 ~ 120 Hz) |
|||||
|
Voltage |
380 ~ 460 V 3 |
|||||
|
Input Ratings |
Voltage |
3 Phase, 380 ~ 460 V (± 10 %) |
||||
|
Frequency |
50 ~ 60 Hz (± 5 %) |
|||||
|
Dynamic |
Braking Circuit |
Optional (Braking Unit, Resistor) |
||||
|
Max. Braking Torque |
150% |
|||||
|
Max. Continuous Baking Time |
Controlled by Braking Unit |
|||||
|
Max. Duty |
10 % ED |
|||||
|
Weight [lbs] |
45 |
45 | 63 | 63 | 68 | |
Common:
|
CONTROL |
Control Method |
V/F Control, Sensorless Vector Control (Selectable) |
||
|
Frequency Setting Resolution |
Digital Reference: 0.01 Hz (Below 100 Hz), 0.1 Hz (Over 100 Hz) |
|||
|
Frequency Accuracy |
Digital: 0.01 % of Max. Output Frequency |
|||
|
V/F Ratio |
Linear, Squared Pattern, User V/F |
|||
|
Overload Capacity |
150 % of Rated Current for 1 Min., 200% of Rated Current for 0.5 sec. (Characteristic is Inversely Proportional to Time) |
|||
|
Torque Boost |
Manual Torque Boost (0 ~ 20 %), Auto Torque Boost |
|||
|
OPERATION |
Input Signal |
Operation Method |
Key / Terminal / Communication Operation |
|
|
Frequency Setting |
Analog: 0 ~ 10V / 4 ~ 20mA / Additional port for Sub-Board (0 ~ 10V) |
|||
|
Start Signal |
Forward, Reverse |
|||
|
Multi-Step |
Up to 8 Speeds can be Set (Use Multi-Function Terminal) |
|||
|
Multi Step Accel/Decel Time |
0 ~ 6,000 sec, Up to 4 Types can be Set and Selected for Each Setting (Use Multi- Function Terminal) |
|||
|
Emergency Stop |
Interrupts the Output of Inverter |
|||
|
Jog |
Jog Operation |
|||
|
Auto Operation |
Operates from Internal Sequence by Setting Multi-Function Terminal (5 Way * 8 Step) |
|||
|
Fault Reset |
Trip Status is Removed when Protection Function is Active |
|||
|
Output Signal |
Operating Status |
Frequency Detection Level, Overload Alarm, Stalling, Over Voltage, Under Voltage, Inverter Overheating, Running, Stop, Constant Speed, Inverter By-Pass, Speed Searching, Auto-Operation Step, Auto-Operation Sequence |
||
|
Fault Output |
Contact Output (30A, 30C, 30B) – AC250V 1A, DC30V 1A |
|||
|
Indicator |
Choose 1 from Output Frequency, Output Current, Output Voltage, DC Voltage |
|||
|
Operation Function |
DC Braking, Frequency Limit, Frequency Jump, Second Function, Slip Compensation, Reverse Rotation Prevention, Auto Restart, Inverter By-Pass, Auto-Tuning, PID Control |
|||
|
Protective Function |
Inverter Trip |
Over Voltage, Under Voltage, Over Current, Fuse Open, Ground Fault, Inverter Overheating, Motor Overheating, Output Phase Open, |
||
|
Inverter Alarm |
Stall Prevention, Overload Alarm, Temperature Sensor Fault |
|||
|
Momentary Power Loss |
Less than 15msec: Continuous Operation, |
|||
|
Display |
Keypad |
Operation Information |
Output Frequency, Output Current, Output Voltage, Frequency Value Setting, Operating Speed, DC Voltage |
|
|
Trip Information |
Indicates a Fault when the Protection Function activates, Retains Up to 5 Faults |
|||
|
Environment |
Ambient Temperature |
-10 °C ~ 40 °C (14 °F ~ 104 °F) |
||
|
Storage Temperature |
-20 °C ~ 65 °C (-4 °F ~ 149 °F) |
|||
|
Ambient Humidity |
90 % RH Max.(Non-Condensing) |
|||
|
Altitude - Vibration |
Below 1,000m or 3,300ft · Below 5.9m/sec˛(=0.6g) |
|||
|
Application Site |
No Corrosive Gas, Combustible Gas, Oil Mist, or Dust |
|||
|
Cooling Method |
Forced Air Cooling |
|||
ORDERING INFORMATION
| 230V | ||
| Model | Motor Rating | |
|
HP |
kW |
|
| CI-001-S2 |
1 |
0.75 |
| CI-002-S2 |
2 |
1.5 |
| CI-003-S2 |
3 |
2.2 |
| CI-005-S2 |
5 |
3.7 |
| CI-007-S2 |
7.5 |
5.5 |
| CI-010-S2 |
10 |
7.5 |
| CI-015-S2 |
15 |
11 |
| CI-020-S2 |
20 |
15 |
| CI-025-S2 |
25 |
18.5 |
| CI-030-S2 |
30 |
22 |
| 460V | ||
| Model | Motor Rating | |
|
HP |
kW |
|
| CI-001-S4 |
1 |
0.75 |
| CI-002-S4 |
2 |
1.5 |
| CI-003-S4 |
3 |
2.2 |
| CI-005-S4 |
5 |
3.7 |
| CI-007-S4 |
7.5 |
5.5 |
| CI-010-S4 |
10 |
7.5 |
| CI-015-S4 |
15 |
11 |
| CI-020-S4 |
20 |
15 |
| CI-025-S4 |
25 |
18.5 |
| CI-030-S4 |
30 |
22 |