DL Series
One Pair - DIN Rail Mountable
Surge Protectors
FEATURES
|
Ultra fast response time | |
|
Multiple stage circuitry | |
|
Resets Automatically | |
|
Can be easily mounted on a DIN Rail DR1 | |
|
Plug- in module |
DESCRIPTION
Citel DL Series has been designed to protect telephone and data lines against lightning surges and electrical transients. Its large power handling and fast response time will protect your sensitive equipment against the worst lightning surges.
It uses state of the art multi-stage circuitry which consists of heavy duty three element gas tubes and solid state diodes that automatically reset after every electrical surge. Under the most severe conditions, the Citel DL Series will fail short leaving your equipment fully protected.
SPECIFICATIONS
| Model: | DL170 | DL48 | DL24 | DL12 | DL06 |
| Application: | Telephone Lines |
Leased Lines |
4
- 20mA Loop Lines |
Telemetry Load Cells |
RS485,
RS422 RTD's, THC's |
| Series Resistance: | 4.7 Ohm | 4.7 Ohm | 4.7 Ohm | 4.7 Ohm | 4.7 Ohm |
| Capacitance: | 70 pF | 200 pF | 300 pF | 400 pF | 900 pF |
| Maximum Line Current: | 200 mA | 200 mA | 200 mA | 200 mA | 200 mA |
| Maximum Line Voltage: | 170 V | 48 V | 24 V | 12 V | 6 V |
| Clamping Voltage: | 190 V | 60 V | 30 V | 20 V | 12 V |
| Power Handling: (8/20us- 10 x's) (8/20us- 1 x 's) |
10 kA 20 kA |
10 kA 20 kA |
10 kA 20 kA |
10 kA 20 kA |
10 kA 20 kA |
| End of
Life Characteristics: (U=220/Veff/Icc>10A) |
Short Circuit |
Short Circuit |
Short Circuit |
Short Circuit |
Short Circuit |
|
Mechanical
Diagram
Mounting: DIN
Rail - DR1 |
Electrical
Diagram
Gt: Three Element Gas Tube |