DS150VG
Direct Strike
Surge Protector
FEATURES
|
40kA transient amps protection (8/20µs) | |
|
15kA transient amps protection (10/350µs) | |
|
Suitable for installation on AC power lines | |
|
Fault indicators and remote alarm | |
|
35mm DIN Rail mounting | |
|
10-Year warranty |
DESCRIPTION
Citel’s DS150VG is designed to protect against direct and indirect effects of lightning. The device is extremely rugged for application in high lightning density areas where the risk of heavy surge current or even direct strikes is a serious concern. It can be configured for both single and three phase networks.
This DS150VG is designed to withstand 15kA (10/ 350us) which is similar to a direct lightning strike. The unique MOV-GDT hybrid design produces no follow current (If) after the surge and no leakage current in stand-by mode. The residual voltage produced is less than 600V.
The DS150VG is UL recognized and is equipped with a thermal disconnection mechanism, remote alarm, and fault indicators.
SPECIFICATIONS
| DS150G | -120 | -300 |
| System Voltage | 120/208V 120/240V |
220/308V 240/415V 240V 277/480V |
| MCOV | 150V | 330V |
| Ipeak 8/20µs | 40kA | 40kA |
| Ipeak 10/350µs | 15kA | 15kA |
| ClampV @ 10kA | <400V | 750V |
| Leakage Current | <2mA | <2mA |
| Diagnostics | Fault indicator and remote alarm |
| Housing Materials | Polycarbonate UL94-5A |
| Operating Temperature | -40°C to +85°C |
| Operating Altitude | 13,000 ft (400M) |
| Connection Method | Parallel |
| Protection Type | MOV-GTD based |
| Connection | screw terminals, 2.5-50mm2 |
| Protection Modes | L-N; L-G; N-G; L-L |
| Dimensions | 90Hx36Wx67D (in mm) |
WIRING DIAGRAM