DR6305
3 Ø PHASE MONITOR
TRANSMITTER/ALARM
FEATURES
|
±0/20 mA Output | |
|
Indicates Lost Phase | |
|
Indicates Phase Reversal | |
|
Jumper Selectable Input (300/600 VAC) | |
|
3 way, 1500 VAC Isolation | |
|
DIN Rail Case | |
|
Low Power Requirement (10-30 VDC @ 1.5 watt) | |
|
UL/cUL Recognized |
DESCRIPTION
The DR6305 Phase Monitor is a
multifunctional measurement instrument that provides: Measurement of the voltage of 2
phases of a 3 phase power line to determine if all phases are present. The
instrument outputs 0/20 mA and 0/-20 mA representing voltage for phase A to
B and C to B respectively. One output switches between the 2 currents
every 5 seconds. Only one bipolar input on the PLC is required to read
voltage levels. An optically isolated transistor
switch output if voltage drops below preset level. An optically isolated transistor
switch for the indication of proper phase rotation. An LED display to indicate
|
which current is being output
| phase loss
| phase reversal |
The DR6305 monitors either 240 VAC or 480 VAC, 3 phase and provides DC output current proportional to the voltage of Phase A and Phase C referenced to Phase B. The DC output current alternates every 5 seconds between positive and negative to indicate A to B or C to B voltages respectively. This allows monitoring of 3 phase voltages with a single bipolar analog measuring device.
The voltage level is monitored and levels below a preset level are indicated by an optically isolated transistor switch output. An LED also indicates low voltage. Phase angle is monitored and phase reversal is indicated by an optically isolated transistor switch output. An LED to indicate phase reversal is also provided.
Internal jumpers allow the product to be used to monitor 240 V or 480 V power systems.
SPECIFICATIONS
POWER
10 to 30 VDC
1.5 watt
INPUT
300VAC or 600VAC Full Scale
Jumper Selectable
OUTPUTS
Proportional Output -
0/20 mADC at 300/600 VAC input between Phase A and Phase B
0/-20 mADC at 300/600 VAC input between Phase C and Phase B
(Switches between positive and negative every 5 seconds)
Optically isolated NPN
transistor, normally closed, turns off on low phase voltage
(<190 VAC or <380 VAC depending on input selection).
Transistor is saturated switch, 50mA maximum current, 30 VDC
maximum voltage.
Optically isolated NPN
transistor, normally closed, turns off on phase reversal.
Transistor is saturated switch, 50mA maximum current, 30 VDC
maximum voltage.
INDICATORS (LED):
Channel being output (AB or CB)
Phase Loss or Low Voltage < 190 V (or 380 V)
Phase Reversal
CONTROLS
Zero and Span adjustments for each channel
Switch to lock channel in AB or CB during calibration
All controls available on front panel
ISOLATION
Three way transformer isolation
Between the 3 Phase AC input voltage, output signal, and the DC power supply
voltage
At least 1500 VAC sine wave.